Voltage Drop Calculator

Drop for a cable run, and the smallest size that passes. Imperial and metric units, change any unit beside its field.

Measurements

About this calculator

Voltage drop on a branch or sub-main cable for single- and three-phase supplies, plus the smallest conductor that keeps you within your limit.

How it’s calculated

VD = 2 × K × I × L ÷ CM for single-phase, or √3 for three-phase. K = 12.9 for copper, 21.2 for aluminum; L in feet; CM is the circular-mil area.

Worked example

With these inputs:

Supply
240 V single-phase
Load current (A)
30
One-way cable length
100 ft
Conductor
Copper
Conductor size
10 AWG
Allowed drop (%)
3

the result is:

Voltage drop
7.46 V (3.11%)
Voltage at load
232.5 V
Smallest size for ≤3% drop
8 AWG

Tips from the trade

  • The Canadian Electrical Code (Rule 8-102) limits voltage drop to 3% in a feeder or branch circuit, and 5% in total from the supply side of the service to the point of use.
  • Long runs to outbuildings and EV chargers are where voltage drop usually decides the cable size.

Results are estimates for planning and pricing. Check quantities against your drawings, the manufacturer’s data and the building code adopted in your province before ordering.