Voltage Drop Calculator

Drop for a cable run, and the smallest size that passes. US units, change any unit beside its field.

Measurements

About this calculator

Voltage drop on a branch or sub-main cable for single- and three-phase supplies, plus the smallest conductor that keeps you within your limit.

How it’s calculated

VD = 2 × K × I × L ÷ CM for single-phase, or √3 for three-phase. K = 12.9 for copper, 21.2 for aluminium; L in feet; CM is the circular-mil area.

Worked example

With these inputs:

Supply
240 V single-phase
Load current (A)
30
One-way cable length
100 ft
Conductor
Copper
Conductor size
10 AWG
Allowed drop (%)
3

the result is:

Voltage drop
7.46 V (3.11%)
Voltage at load
232.5 V
Smallest size for ≤3% drop
8 AWG

Tips from the trade

  • NEC informational notes suggest 3% for a branch circuit and 5% total.
  • Long runs to outbuildings and EV chargers are where voltage drop usually decides the cable size.

Results are estimates for planning and pricing. Check quantities against your drawings, the manufacturer’s data and local building codes before ordering.