Air Conditioner Size Calculator

Split system size in kW for a room. Metric units, change any unit beside its field.

Measurements

About this calculator

Quick sizing for a reverse-cycle split system in kW for one room, adjusted for climate, sun, insulation and ceiling height.

How it’s calculated

kW = floor area × a climate rate (about 0.13–0.17 kW per m²) × ceiling height ÷ 2.4 m, adjusted for sun and insulation. The result is rounded up to the next common split system size: 2.0, 2.5, 3.5, 5.0, 6.0, 7.1, 8.0 or 9.0 kW.

Worked example

With these inputs:

Room length
4.5 m
Room width
3.8 m
Ceiling height
2.4 m
Climate
Warm (e.g. Sydney, Adelaide, Perth)
Sun on the room
Average
Insulation
Average

the result is:

Cooling capacity
2.6 kW
Room area
17.1 m²
Base rate
150 W per m²
In BTU/h
8,752

Tips from the trade

  • Oversized AC short-cycles and leaves rooms clammy, so bigger is not better.
  • Open-plan areas count as one room. Measure the whole space the unit has to cool, not just the part it faces.

Common questions

What size air conditioner for a 30 m² room?

About 4.5 kW in a warm climate with average insulation, so a 5.0 kW split system.

Results are estimates for planning and pricing. Check quantities against your drawings, the manufacturer’s data and the NCC and Australian Standards before ordering.