Roof Space Ventilation Calculator

Eaves and high-level vents to NCC 10.8.3. Metric units, change any unit beside its field.

Measurements

About this calculator

Work out the roof space ventilation the NCC 2022 condensation provisions ask for in climate zones 6, 7 and 8, and count vent strips.

How it’s calculated

Under NCC 2022 Housing Provisions 10.8.3: below 10°, provide 25,000 mm² per metre at each of two opposing ends. From 10° to under 15°, 25,000 mm²/m at the eaves plus 5,000 mm²/m at high level. From 15°, 7,000 mm²/m at the eaves (25,000 with a cathedral ceiling) plus 5,000 mm²/m at high level.

Worked example

With these inputs:

Total eaves length (both sides)
20 m
Ridge length
10 m
Roof pitch (degrees)
22.5
Cathedral (raked) ceiling
No

the result is:

Eaves (low-level) openings
7,000 mm² per metre
High-level openings
5,000 mm² per metre = 50,000 mm²

Tips from the trade

  • Baffles or rafter trays keep insulation from blocking the eaves.
  • Don’t mix ridge vents with gable or powered vents on the same attic. They short-circuit each other.

Results are estimates for planning and pricing. Check quantities against your drawings, the manufacturer’s data and the NCC and Australian Standards before ordering.