Home/Roofing/Roof Ventilation Calculator

Roof Ventilation Calculator

Eaves and high-level vent requirements. Metric units, change any unit beside its field.

Measurements

About this calculator

Work out the eaves and high-level ventilation for a cold pitched roof using the common BS 5250 provisions, and count vent strips.

How it’s calculated

Pitches of 15° and above get 10 mm continuous ventilation at each eave. Below 15° it rises to 25 mm. With traditional HR felt, or on steep pitches, add 5 mm continuous high-level ventilation at the ridge.

Worked example

With these inputs:

Total eaves length (both sides)
20 m
Ridge length
10 m
Roof pitch (degrees)
35
Underlay
Traditional felt (HR)

the result is:

Eaves ventilation
10 mm continuous
High-level (ridge) ventilation
5 mm continuous = 50,000 mm²

Tips from the trade

  • Baffles or rafter trays keep insulation from blocking the eaves.
  • Don’t mix ridge vents with gable or powered vents on the same attic. They short-circuit each other.

Results are estimates for planning and pricing. Check quantities against your drawings, the manufacturer’s data and the Building Regulations before ordering.